JOINT ORDER OF THE MINISTER OF INTERNAL AFFAIRS OF THE REPUBLIC OF KAZAKHSTAN AND MINISTER OF NATIONAL ECONOMY OF THE REPUBLIC OF KAZAKHSTAN

of September 1, 2020 No. 610, on September 2, 2020 No. 61

About modification and amendments in the joint order of the Minister of Internal Affairs of the Republic of Kazakhstan of October 30, 2018 No. 758 and the Minister of national economy of the Republic of Kazakhstan of October 30, 2018 No. 31 "About approval of criteria for evaluation of risk degree and checking sheets in the field of fire safety and civil defense"

According to Item 1 of article 143 of the Entrepreneurial code of the Republic of Kazakhstan of October 29, 2015, we ORDER:

1. Bring in the joint order of the Minister of Internal Affairs of the Republic of Kazakhstan of October 30, 2018 No. 758 and the Minister of national economy of the Republic of Kazakhstan of October 30, 2018 No. 31 "About approval of criteria for evaluation of risk degree and checking sheets in the field of fire safety and civil defense" (it is registered in the Register of state registration of regulatory legal acts for No. 17647, it is published on November 15, 2018 in Reference control bank of regulatory legal acts of the Republic of Kazakhstan) the following changes and amendments:

in Criteria for evaluation of risk degree, the conducting the checks in the field of fire safety approved by the specified joint order applied to special procedure:

in item 4:

4) to state the subitem in the following edition:

"4) buildings of the Supreme Court of the Republic of Kazakhstan, courts of areas, cities of republican value and capital, areas (cities of regional value);";

6) to state the subitem in the following edition:

"6) objects of bodies of homeland security, defense, Service of the state protection of the Republic of Kazakhstan;";

14) to state the subitem in the following edition:

"14) gas storages, gas-holder, gas-distributing and gas-accumulating stations;";

26) and 27) to state subitems in the following edition:

"26) archives, libraries;

27) objects of trade and entertainment centers (the single building or complex of buildings and constructions of single object) - with a total area of structures 1500 and more square meters;";

31) to state the subitem in the following edition:

"31) automobile fuel and gas-filling stations (stationary and portable);";

36) to state the subitem in the following edition:

"36) office buildings and multipurpose complexes (the single building or complex of buildings and constructions of single object) - with a total area of 1500 and more square meters, and also irrespective of the area more than 28 meters high;";

in Item 5:

16) and 17) to state subitems in the following edition:

"16) objects of trade and entertainment centers (the single building or complex of buildings and constructions of single object) - with a total area of structures less than 1500 square meters;

17) office buildings and multipurpose complexes (the single building or complex of buildings and constructions of single object) - with a total area less than 1500 square meters;";

19) to exclude the subitem;

state Item 8 in the following edition:

"8. In special procedure for conducting checks the objects specified in the subitem 6) of item 4 of these Criteria are checked during the period from August to September, in the subitem 19) of item 4 of these Criteria during the period from February to May, in subitems 23) and 39) of item 4 of these Criteria during the period from April to June, in the subitem 22) of item 4 of these Criteria during the period from July to August, in subitems 8), 9), 10) and 12) of item 4 of these Criteria during the period from July to August, in the subitem 24) of item 4 of these Criteria during the period from October to November of the planned year.";

Appendix to the specified Criteria to be reworded as follows according to appendix 1 to this joint order;

in the Criteria for evaluation of risk degree for carrying out preventive control with visit in the field of civil defense approved by the specified joint order:

third item 4 to state the paragraph in the following edition:

"local executive bodies of areas, cities of republican value and capital, cities and districts of areas;";

the paragraph one of Item 15 to state in the following edition:

"15. On risk exponents the checked subject (object) of control belongs:";

to be reworded as follows appendix to the specified Criteria according to appendix 2 to this joint order;

to be reworded as follows the checking leaf in the field of the state control in the field of fire safety concerning objects irrespective of category, purpose and type of activity approved by the specified joint order according to appendix 3 to this joint order;

to be reworded as follows the checking leaf in the field of the state control in the field of fire safety concerning the autocompanies, objects of servicing of transport, car parks (parkings) approved by the specified joint order according to appendix 4 to this joint order;

in the Checking leaf in the field of the state control in the field of fire safety concerning office buildings (multipurpose complexes), apartment (individual) apartment houses and hostels, the approved specified joint order:

add with Item 12 of the following content:

     "

12

Non-admission of storage on balconies and loggias in apartments and living rooms of flammable and combustible liquids, gas cylinders










 

";

in the Checking leaf in the field of the state control in the field of fire safety concerning houses and rest areas, summer recreation camps and tourist bases, the approved specified joint order:

state Item 5 in the following edition:

     "

5

Placement non-admission more than 50 children in buildings and constructions of IV and V degrees of fire resistance










 

";

add with Items 10, 11 and 12 following contents:

     "

10

Availability of the mineralized fire-proof strips at least 4 meters wide on perimeter behind barrier from the forest area, in the territory of places of summer holiday of the children located in forests or is direct in proximity from them










11

Availability of the plan of organizational and technical actions for ensuring fire safety and the scheme of the camp (base) on which all buildings, the places of residence of people (apartment houses, constructions, tents, yurtas), places of economic appointment, sources of outside fire-water supply, the parking of cars, trail cars are specified. Placement of the scheme on entrance on the territory of the camp (base)









12

The device in the territory of places of flight rest of children and recreation camps of tents (yurtas) the territory space the occupied one group (1 or 2 rows) of no more than 800 square meters. Providing distance between groups at least 15 meters, and between tents (yurtas) – is at least 2,5 of meters









 

";

in the Checking leaf in the field of the state control in the field of fire safety concerning cultural and spectacular, entertaining and sports facilities, the approved specified joint order:

state Item 2 in the following edition:

     "

2

Availability of the test report processed wooden designs of scenic box (grid-irons, scene flooring, suspended bridges, working galleries) by deep impregnation by fire-retarding agents, and also combustible scenery, scenic and exhibition registration, draperies in visual and exposition halls, the foyer, buffets. Availability of the test report of the processed designs










 

";

in the Checking leaf in the field of the state control in the field of fire safety concerning objects of the oil-and-gas and oil and gas processing industry, the approved specified joint order:

state Item 88 in the following edition:

     "

88

Availability of the magazine of operation of lightning protection devices with mark of survey of lightning protection devices at least once a year during season preceding a storm










 

";

in the Checking leaf in the field of the state control in the field of fire safety concerning objects of trade, the approved specified joint order:

state Item 16 in the following edition:

     "

16

Placement in the taken-away territory groups of booths, and also one-storey pavilions up to 35 square meters inclusive. Placement in one group no more than 20 booths and pavilions I, II, III, IIIA of degree of fire resistance or 10 – IIIA, IV, IVA and the V degrees of fire resistance.
Separation of group of 10 containers fire-proof partitions of the 1st type.
Distance availability between groups, between separate pavilions and booths, and also from groups and separate pavilions and booths to other buildings and constructions










 

";

 

checking leaf in the field of the state control in the field of civil defense concerning the organizations referred to category on civil defense and based on which services of civil protection, approved by the specified joint order are created to be reworded as follows according to appendix 5 to this joint order;

to be reworded as follows the checking leaf in the field of the state control in the field of civil defense concerning local executive bodies of the Republic of Kazakhstan approved by the specified joint order according to appendix 6 to this joint order;

to be reworded as follows the checking leaf in the field of the state control in the field of civil defense concerning the central executive bodies and their territorial subdivisions approved by the specified joint order according to appendix 7 to this joint order.

2. To provide to committee on emergency situations of the Ministry of Internal Affairs of the Republic of Kazakhstan in the procedure established by the legislation:

1) state registration of this joint order in the Ministry of Justice of the Republic of Kazakhstan;

2) placement of this joint order on Internet resource of the Ministry of Internal Affairs of the Republic of Kazakhstan;

3) within ten working days after state registration of this order in the Ministry of Justice of the Republic of Kazakhstan submission to Legal department of the Ministry of Internal Affairs of the Republic of Kazakhstan of data on execution of the actions provided by subitems 1) and 2) of this Item.

3. To impose control of execution of this joint order on the supervising deputy minister of internal affairs of the Republic of Kazakhstan.

4. This joint order becomes effective after ten calendar days after day of its first official publication.

Minister of national economy of the Republic of Kazakhstan

R. Dalenov

Minister of Internal Affairs of the Republic of Kazakhstan

E.Turgumbayev

 

"Is approved"

Committee on legal statistics and special accounting of the Prosecutor General's Office of the Republic of Kazakhstan

 

Appendix 1

to the Joint order of the Minister of national economy of the Republic of Kazakhstan of September 2, 2020 No. 61 and the Minister of Internal Affairs of the Republic of Kazakhstan of September 1, 2020 No. 610

Appendix

to the Criteria for evaluation of risk degree applied to special procedure for conducting checks in the field of fire safety

Distribution of violations of requirements of fire safety to rough, considerable, insignificant degrees

 

№ of payment order

The name of requirements of fire safety (severity is established in case of non-compliance with the specified requirement)

Extent of violations

1. Requirements to organizational actions

1

Availability of the instruction establishing the fire prevention regime corresponding to its fire risk for object

insignificant

2

Availability of plans of evacuation of people in case of fire

insignificant

3

Availability of responsible persons for ensuring fire safety on certain sites of works

insignificant

4

Availability of the official responsible for operation of fire protection systems, acquisition, repair, safety and readiness for action of emergency firefighting equipment, timely and high-quality carrying out maintenance (reloading of manual fire extinguishers) and scheduled preventive maintenance

insignificant

5

Availability of the special magazine or the automated system on accounting of works on maintenance and scheduled preventive maintenance of technical means of fire protection systems, verifications of presence and conditions of emergency firefighting equipment

insignificant

6

Availability of the instruction, instruction sheet of measures of the fire safety developed for buildings with the round-the-clock stay of people (boarding schools, nursing homes and disabled people, orphanages, hospitals, hotels, motels, campings), with option of independent evacuation of people, and also evacuations of people incapable of independent evacuation, personnel of the organization for light and night-time

insignificant

7

Implementation by heads of boarding schools, nursing homes and disabled people, orphanages and hospitals at least once in half-year of trainings of personnel on their actions in case of the fire with simultaneous check of operability of all elements of the fire protection system of the building

insignificant

8

Availability at personnel on duty in case of itself set of keys from all locks of doors of the building, agrees the functions assigned to it. Storage of reserve set of keys in personnel (protection) on duty on the first floor of the building

insignificant

9

Availability at servicing or personnel of buildings on duty for accommodation of people, objects with mass stay of people, electric lamps on electricity outage case

insignificant

10

Availability in settlements of the rural zone, gardening partnerships, country cooperatives (partnerships, consumer cooperatives, non-profit partnerships) in the territory of which divisions of fire service, fire motor-pumps with set of sleeves and trunks, emergency firefighting equipment, the nonmechanized tool and fire stock which are used in case of suppression of the fires are not placed

considerable

11

Availability in the territory of rural settlements, gardening partnerships, country cooperatives, block and container buildings of means of the sound alarm system for the notification of people about the fire, stock holding of water for the purposes of fire extinguishing

considerable

12

The admission to work of workers after passing of fire-proof instructing and passing of the subsequent training in the program of fire and technical minimum

insignificant

13

Availability of non-state fire service

rough

2. Requirements to content of the territories

14

Availability of entrances for fire trucks to buildings, constructions, technological installations, sources of fire-water supply

considerable

15

Availability of stationary post with the round-the-clock watch of personnel, and the barrier provided with the device for their manual opening in case of installation at entrance on the territory of groups of the apartment houses combined by general space (yard) of barrier

insignificant

16

Non-admission of blocking up of fire-proof distances between buildings and constructions, materials and the equipment, parking of transport and construction (installation) of buildings and constructions

considerable

17

Availability of fire-proof distances

rough

18

Non-admission cultivation of fires, burning of waste and container at distance less than 50 meters from buildings and constructions. Non-admission of installation of special devices for placement of the burning coal (brazier, barbecue, grill) in places with dry vegetation, under crowns, under the canopies made of combustible materials in rooms of the residential building, and also on balconies and loggias, in economic constructions, garages, attics, on flat roofs

considerable

19

Non-admission of the device in the territory of settlements and the organizations of dump of combustible waste

considerable

20

Non-admission of use of naked flame and smoking on explosion-fire-hazardous sites of the territory, buildings and constructions

rough

21

Availability in the buildings and constructions which are not belonging to the category of the explosion-fire-hazardous objects specially allotted and the equipped smoking areas

insignificant

22

Cleaning of the territory of combustible waste, garbage, container, fallen leaves, combustible garbage and other combustible materials

considerable

23

Availability of outside lighting in the territory of the organization in night-time for bystry finding of fire hydrants, outside fire-escapes and locations of fire stock, and also entrances to piers of fire reservoirs, to entrances to buildings and constructions

considerable

24

Placement of temporary structures from under construction and other buildings at distance at least 18 meters or at blank fire-proof walls

considerable

25

Placement of certain block and container buildings and household cars by groups no more than 10 in group and no more than 800 m 2, with distance between groups of these buildings and from them to other structures at least 18 meters

considerable

26

Development and accomplishment of the actions excluding possibility of spread of fire in case of wildfires on buildings and constructions (the device of protective fire-proof strips, landing of deciduous plantings, removal during the summer period of dry vegetation)

rough

3. Requirements to content of buildings, constructions and structures

27

Placement on doors of emergency exits from rooms, buildings (constructions) of production and warehouse appointment, on outside technological installations of information on their category on fire and explosion and fire risk, and also about classes of the explosive or fire hazardous zones located in them

insignificant

28

Availability, compliance of the project documentation and content in the serviceable working condition of installations of fire extinguishing and the fire alarm, warning systems and managements of evacuation of people in case of the fire, antismoke protection and fire-water supply, fire-proof doors, valves, hatches and other fillings of apertures in fire-proof barriers, rooms, buildings and constructions, remedies and rescuing of people

rough

29

Non-admission of work on the equipment, installations and machines with defects

rough

30

Availability in the buildings, constructions and structures provided by the project, operational devices of lightning protection

rough

31

Content in good repair mechanisms for self-closing of doors. Non-admission of installation of any devices interfering free closing of fire-proof doors and antismoke devices (curtains, screens, curtains)

rough

32

Providing hotels, multipurpose buildings more than 50 meters high with fireproof zones, according to the project documentation

rough

33

Providing people of the hotels which are in rooms, multipurpose and office buildings located at the height more than 28 meters, individual protection equipment of respiratory organs and sight (self-rescuers) in the quantity established by the project documentation

rough

34

Providing hotels, motels, multipurpose buildings more than 50 meters high with individual and collective survival equipment, according to the project documentation

rough

35

Non-admission of the device in staircases and corridors of storage rooms (utility rooms), and also storage under ladder marches and on landings of things, furniture and other combustible materials

rough

36

Availability of fireproof processing and coverings of building constructions, finishing heat-insulating materials, air ducts, metal support and platforms, wooden designs and implementation of check of condition of fireproof processing (impregnation), with creation of the test report

rough

37

Ensuring closing on the lock of doors of garrets, and also technical floors and cellars in which under the terms of technology permanent stay of people is not required. Availability on doors of the specified rooms of information on the storage location of keys

insignificant

38

Non-admission of use of attics, technical floors, air-ventilation chambers and other technical rooms for the organization of production sites, workshops, and also storages of products, the equipment, furniture and other objects

rough

39

Cleaning of garbage and other objects of priyamk at window openings of basement and first floors of buildings, constructions and structures, opening of locks at windows from within without key

rough

40

Non-admission of the device of lattices at windows of all floors of the building, and priyamka at windows of cellars (except for premises of the correctional and special facilities providing temporary isolation from society, warehouses, cash desks, weapon rooms, confidential parts of organizations, storage and the address of precursors)

rough

41

Non-admission of placement in lift halls of storage rooms, booths, stalls

rough

42

Non-admission of glazing of balconies, loggia and galleries relating to safety areas on fire case

rough

43

Non-admission of changes of space-planning decisions as a result of which conditions of safe evacuation of people worsen access to fire extinguishers, fireplugs and other means of fire safety is limited or the zone of operations of automatic fire protection systems decreases (the automatic fire alarm, stationary automatic installation of fire extinguishing, system of smoke removal, the warning system and management of evacuation)

rough

44

Non-admission of storage and application in basement and first floors of flammable and combustible liquids, gunpowder, explosives, cylinders with gases, goods with aerosol package, tselluloida and other explosion-fire-hazardous substances and materials

rough

45

Non-admission of removal, the doors of emergency exits provided by the project from floor-by-floor corridors, halls, the foyer, platforms and staircases, other doors interfering distribution of dangerous factors of the fire on the ways of evacuation

rough

46

Non-admission of the device in production and storage facilities of buildings (except buildings of the V degree of fire resistance) mezzanines, partitions, change houses, storerooms and other built-in rooms from combustible materials

rough

47

Non-admission of simultaneous stay of 50 people and more in rooms with one emergency exit

rough

48

Availability of required quantity of the operational and undergone maintenance emergency firefighting equipment

considerable

49

 Seal by the construction solution or other nonflammable materials providing the required limit of fire resistance and dymogazonepronitsayemost formed openings and gaps in places of crossing of fire-proof walls, overlappings and the protecting designs with different engineering and technological communications

rough

50

Non-admission of change of functional purpose, carrying out capital repairs, modernization, reconstruction and re-planning of buildings, constructions and structures without the developed and approved design estimates

considerable

51

Availability, content in good repair and exposure to operating tests of outside fire-escapes and barriers on roofs of buildings, constructions and structures

rough

52

In case of operation of household gas appliances non-admission of placement of furniture and other combustible materials at distance of less 0,2 of meters across to the closest vertical surface of less 0,7 of meters down to the next horizontal surface of these products hanging over it

rough

53

Non-admission of arrangement of gas cylinders (working and reserve) for supply with gas of household gas appliances (including stoves, boilers, geysers) in buildings

rough

4. Requirements to content of evacuation ways and exits

54

Non-admission in buildings with stained-glass windows more than 1 meter of violations high of designs of the smoke-tight nonflammable diaphragms established in stained-glass windows at the level of each floor

considerable

55

Automatic lowering on the main landing floor, and in underground constructions raising on upper floor and de-energization of elevators and elevators (except for fire elevators) in case of the fire

rough

56

Availability of the warning signs of fire safety with text "Flammablly. Cylinders with gas" at entrance to buildings (including individual apartment houses) or constructions in which gas cylinders are stored or used

insignificant

57

Availability on subject of certificates (declarations) on confirmation of conformity of limit of fire resistance, class of fire risk of building constructions (including designs of filling of apertures), and also indicators of fire risk of construction materials (including, finishing)

considerable

58

Availability on subject of certificates (declarations) on confirmation of conformity of fire safety and fire extinguishing devices

considerable

59

Quantity of emergency exits from buildings, rooms and compliance to their project decision (including on illumination, the sizes and space-planning solutions of evacuation ways and exits, and also availability on the ways of evacuation of signs of fire safety)

rough

60

The device of doors on the ways of evacuation opening freely and in the direction of exit from the building

rough

61

Possibility to the people who are in the building (construction), free opening of locks on doors of emergency exits from within without key

rough

62

Content in good repair and the included light indication of the volume light signs of fire safety "Exit", "Emergency (zapasny) exit", "Door of emergency exit" used on the ways of evacuation

rough

63

Non-admission of blocking up of evacuation ways and exits (including doors, passes, corridors, platforms, galleries, lift halls, landings, marches of ladders, doors, evacuation hatches, transitions to adjacent sections and exits to outside evacuation ladders) different materials, products, equipment, production waste, garbage and other objects, and also clogging of door of emergency exits

rough

64

Non-admission of the device in platforms of exits of dryers and hangers for clothes, clothes, and also storage (including it is temporary) stock and materials

rough

65

Non-admission of the device on the ways of evacuations of thresholds (except for thresholds in doorways), sliding and lifting and lowering doors and gate, revolving doors and tourniquets, and also other devices interfering free evacuation of people in the absence of other (duplicative) ways of evacuation or in the absence of the technical solutions allowing to open and block manually the abroach specified devices

rough

66

Non-admission of use of the combustible materials inappropriate to class of fire risk for finishing, facings and colourings of walls, ceilings and floors, and also steps and landings on the ways of evacuation, except for buildings of the V degree of fire resistance

rough

67

Non-admission of fixation of the self-closed doors of staircases, corridors, halls and platforms in open provision, and also their removal

rough

68

Non-admission of glazing or closing of blinds of air areas in nezadymlyaemy staircases

rough

69

Availability of evacuation passes to staircases and other ways of evacuation in case of arrangement of processing, exhibition and other equipment of the room

rough

70

Fixture to floor of carpets, carpet paths and other coverings of floors in rooms with mass stay of people

rough

5. Requirements to operation of power networks, electroinstallations and electrotechnical products

71

Non-admission of blocking up and closing of passes to installation sites of individual protection equipment and fixtures of rescue devices

rough

72

Non-admission of laying and operation of air-lines of electricity transmission over combustible roofs, canopies, and also ground storages (stacks, ricks) of combustible substances, materials and products

rough

73

Non-admission of use of power networks and receivers of electrical energy with violation of the safety requirements stated in the instruction of manufacturer, electric receivers with defects which can lead to the fire (to cause sparking, short circuit, superadmissible heating of isolation of cables and wires, refusal of automatic management systems, antiemergency and fire protection), and also operation of electric wires and cables with the isolation damaged or lost protective properties

rough

74

Non-admission of use of the damaged and loose sockets, knife switches, other electroadjusting products, operation of the power supply network temporary barracks

rough

75

Non-admission of use of electric heaters in case of absence or defect of the temperature regulators provided by design

rough

76

Non-admission of wrapping of electrolamps and lamps paper, fabric and other combustible materials, and also operation of lamps with the removed plafonds (lenses) and protective grids provided by lamp design

rough

77

Non-admission of use of electroirons, rangettes, electric kettles and other electric heaters without special supports (the socles of food, heating disks) excluding risk of fire if their availability is provided by the instruction of manufacturer

rough

78

Non-admission of use of electric heaters in all explosion-fire-hazardous and fire-dangerous rooms

rough

79

Non-admission of use of non-standard (self-made) electric heaters, uses of not calibrated fusible inserts or other self-made devices of protection against overloads and short circuit

rough

80

Non-admission of placement (warehousing) at electric boards, electric motors and the starting equipment, in rooms and corridors of the closed distributing devices, combustible substances and materials (including flammable)

rough

81

 Non-admission of application in fire hazardous zones of the electric equipment which does not have designations of level and appearance of protection of manufacturing plant against explosion and (or) the fire

rough

82

Check of condition of the stationary equipment and electrical wiring of emergency and working light, testing and measurement of resistance of isolation of wires, cables and the grounding devices at least once in three years

rough

83

Installation of all current carrying parts, distributing devices, devices and measuring devices, and also safety devices of explosive type, knife switches, and all other starting devices and devices of electroinstallations only on the nonflammable bases (marble, textolite, гетинакс)

rough

84

Accomplishment of connection, okontsevaniye and branch of veins of wires and cables in order to avoid dangerous transitional resistance in the fire relation by means of pressure testing, welding, the soldering or special clips

rough

6. Requirements to content of systems of heating and ventilation of buildings and constructions

85

Non-admission of violations of service conditions of the heatgenerating devices, their placement in rooms (places), unadapted for these purposes

rough

86

Removal of products of burning from the heatgenerating devices out of limits of buildings and constructions via the smoke channels which are specially intended for these purposes. Non-admission of use as smoke channels air ducts of system of ventilation

rough

87

Availability in structure of the smoke canal of technological openings for their periodic cleaning of soot

considerable

88

Availability on floor from combustible materials under furnace door of the heatgenerating devices using solid fuel of prefurnace metal leaf the size is at least 0,5 x 0,7 of meters without openings located by its long party along the furnace

considerable

89

Placement of the device using liquid fuel in the metal pallet containing all amount of fuel which is in fuel tank in case of emergency flood

considerable

90

Non-admission of use in premises of the heatgenerating devices using liquid fuel with temperature of flash below 61 °C and also combustible liquid as the heat carrier in systems of heating

rough

91

Availability on the heatgenerating devices using liquid, solid and gaseous fuel, operational doors and fire-proof cutting (отступок) from combustible designs

rough

92

Availability on fuel-supply line about each nozzle of heating coppers and heatgenerating installations at least two gates: one – at fire chamber, another – at reservoir with fuel

considerable

93

In production rooms implementation of fire chamber of the furnaces by specially allocated persons (stokers) instructed about measures of fire safety in case of operation of heating devices

insignificant

94

Cleaning of chimneys, flues and other elements of heating furnaces and systems of soot just before the beginning, and also during the heating season

considerable

95

Non-admission of storage of fuel of the heatgenerating device in the rooms which are not intended for these purposes or out of specially allocated platforms located not closer than 8 meters from combustible structures

rough

96

Non-admission of application in fuel quality of the combustible substances (firm, liquid, gaseous) which are not provided by maintenance instructions of furnaces

rough

97

Non-admission of operation of the heatgenerating installation in case of dribble of liquid fuel, gas leakage from systems of fuel feeding, defective flue and other defects

rough

98

Non-admission of operation in case of absence, defect or shutdown of the heatgenerating installations of devices of control and regulation provided by design

rough

99

Non-admission of drying of clothes and combustible materials on the heatgenerating devices and near them

rough

100

Non-admission of placement of the fuel prepared for burning, and also other combustible substances and materials on prefurnace leaf

rough

101

Non-admission of application for ignition of furnaces on solid fuel of flammable and combustible liquids

rough

102

Non-admission of drying of combustible substances and materials at distance of less 0,5 of meters from the surface of the furnace and flues

rough

103

Availability of the specially allotted places excluding possibility of the fire for placement of ashes and slag and spill their water

rough

104

Non-admission of placement of combustible substances, materials, products and oborudovaniye at distance of less 1,25 of meters to furnace openings of furnaces of less 0,7 of meters to other heated parts of furnaces

rough

105

Whitewashing availability on attics of chimneys and walls in which there pass smoke channels

considerable

106

Availability of spark arresters on chimneys of boiler installations

rough

107

Observance of the instruction of manufacturers, and also requirement of regulations of the designing imposed to systems of heating in case of installation of furnaces of factory production in rooms of hostels, office, public, office and household buildings of industrial enterprises, in apartment houses

considerable

108

Height of legs of temporary metal furnaces is at least meter 0,2

considerable

paid document

Full text is available with an active Subscribtion after logging in.

Disclaimer! This text was translated by AI translator and is not a valid juridical document. No warranty. No claim. More info

Effectively work with search system

Database include more 50000 documents. You can find needed documents using search system. For effective work you can mix any on documents parameters: country, documents type, date range, teams or tags.
More about search system

Get help

If you cannot find the required document, or you do not know where to begin, go to Help section.

In this section, we’ve tried to describe in detail the features and capabilities of the system, as well as the most effective techniques for working with the database.

You also may open the section Frequently asked questions. This section provides answers to questions set by users.