of May 13, 2025 No. 251
About approval of regulatory legal acts in the field of fire safety
For the purpose of increase in level of fire safety and reduction of material damage from the fires, the timely notification of people about the fire and creations of conditions for their successful evacuation, and also protection of life and health of citizens, property from the fires, according to Articles 5, 6 Laws of the Kyrgyz Republic "About fire safety", articles 13, of the 17th constitutional Law of the Kyrgyz Republic "About the Cabinet of Ministers of the Kyrgyz Republic" the Cabinet of Ministers of the Kyrgyz Republic decides:
1. Approve:
1) Fire safety regulations in the Kyrgyz Republic according to appendix 1;
2) the list of the buildings, constructions, rooms and the equipment which are subject to protection by automatic detection systems and fire extinguishing according to appendix 2.
2. To heads of the ministries, the state committee, administrative departments, local government bodies (under approval), local public administrations, other state bodies (under approval), to plenipotentiaries of the President of the Kyrgyz Republic in areas, the organizations to take the necessary measures following from this resolution.
3. Determine that financing of the actions following from implementation of this resolution is performed within the means provided to state bodies and local government bodies for the corresponding year.
1) the order of the Government of the Kyrgyz Republic "About approval of the list of the buildings, constructions, rooms and the equipment which are subject to protection by automatic detection systems and fire extinguishing" of April 29, 2011 No. 196;
2) the order of the Government of the Kyrgyz Republic "About modification of the order of the Government of the Kyrgyz Republic "About approval of the List of the buildings, constructions, rooms and the equipment which are subject to protection by automatic detection systems and fire extinguishing" of April 29, 2011 No. 196" of March 6, 2013 No. 116;
3) Item 7 of the order of the Government of the Kyrgyz Republic "About modification and amendments in some decisions of the Government of the Kyrgyz Republic in the field of ecological and technical safety" of September 10, 2013 No. 509;
4) Item 2 of the order of the Government of the Kyrgyz Republic "About modification of some decisions of the Government of the Kyrgyz Republic for the purpose of reduction in compliance with the Law of the Kyrgyz Republic "About fire safety" of June 11, 2018 No. 277;
5) the order of the Government of the Kyrgyz Republic "About approval of Fire safety regulations in the Kyrgyz Republic" of August 22, 2018 No. 381;
6) the order of the Government of the Kyrgyz Republic "About modification of the order of the Government of the Kyrgyz Republic "About approval of Fire safety regulations in the Kyrgyz Republic" of August 22, 2018 No. 381" of December 15, 2020 No. 607.
5. To impose control of execution of this resolution on management of control of execution of decisions of the President of the Kyrgyz Republic and the Presidential Administration Cabinet of Ministers of the Kyrgyz Republic.
6. This resolution becomes effective after ten days from the date of official publication.
Chairman of the Cabinet of Ministers of the Kyrgyz Republic
A.Kasymaliyev
Appendix 1
to the Resolution of the Cabinet of Ministers of the Kyrgyz Republic of May 13, 2025 No. 251
1. Fire safety regulations in the Kyrgyz Republic (further - Rules) determine the requirements of fire protection regulations establishing rules of conduct of legal entities and physical persons, procedure for production organization and (or) content of the territories, buildings, constructions, premises of the organizations, dwelling stock and other objects (further - subject to protection) for the purpose of ensuring fire safety.
In these rules the following concepts and terms are used:
1) emergency exit - exit (door, the hatch, window) which is intended for evacuation and conducts directly outside or to the safety area and which is used as additional exit for rescue of people, but is not considered in case of assessment of conformity of necessary quantity and the sizes of evacuation ways and exits to conditions of safe evacuation of people in case of the fire;
2) subject to protection - the property of physical persons or legal entities, the state-owned or municipal property (including the territory, buildings, constructions, vehicles, technological installations, the equipment, aggregates, products and other property) to which are established or shall be established requirements of fire safety;
3) emergency firefighting equipment - the figurative or portable fire extinguishing means used for fight against the fire in initial stage of its development;
4) fire-proof gap (fire-proof distance) - the normalized distance between buildings and (or) constructions established for prevention of distribution of the fire;
5) construction - the volume, plane or linear, land, elevated or underground construction system consisting from bearing, and in some cases and the protecting designs and intended for accomplishment of production processes of different type, storage of materials, products, the equipment, temporary stay of people, movement of people, loads, etc.;
6) technical means of the notification and management of evacuation - set of the technical means (monitors annunciators, fire annunciators) intended for the notification of people about the fire;
7) installation of the fire alarm - set of the technical means intended for detection of the fire, processing, transfer in the set type of the notice on the fire, special information and (or) issues of commands for inclusion of automatic installations of fire extinguishing and smoke removals, the processing and engineering equipment, and also other devices of fire protection;
8) hot work - production operations using naked flame, sparking and heating to temperature capable to cause ignition of materials and designs (electric welding, gas welding, benzo-kerosinorezka, plumbing, machining of metal with formation of sparks, etc.);
9) evacuation - process of organized independent (dependent) movement (movement) of people outside or to the safety area from rooms in which there is possibility of impact on them dangerous factors of the fire;
10) evacuation way (way of evacuation) - way of movement and (or) movement of people, the leader directly outside or to the safety area in case of the fire;
11) emergency exit - the exit conducting on the way of evacuation, directly outside or to the safety area;
12) means of communication - technical base for ensuring processes of collection, processing, accumulating and distribution of information;
13) mobile gas station (MAZS) - gas station, technological system which is installed on the automobile chassis, trail car or semitrailer truck with located on it the reservoir and fuel-dispensing column, intended for delivery of oil products to consumers in case of their retail sale by remote method;
14) electrofuel station - the infrastructure element providing the electric power for charging of the accumulator electric transport, such as electric vehicles, electrobuss, electroscooters, electroscooters, giroskuter, sigve, electrobicycles, etc.
The legal basis of ensuring fire safety are the Constitution of the Kyrgyz Republic, the laws of the Kyrgyz Republic in the field of fire safety, the these rules and other regulatory legal acts regulating the sphere of ensuring fire safety, and also regulation and the rule on designing and construction of facilities establishing requirements to their fire protection.
2. Concerning each subject to protection (except for individual apartment houses) the head (other authorized officer) of the organization (individual entrepreneur) in which use on the property right or on other legal cause there are subjects to protection (further - the head of the organization) the Instruction about measures of fire safety according to appendix 3 to these rules, including separately for each explosion-fire-hazardous and fire-dangerous room of production and warehouse appointment affirms.
3. Heads and officials of the companies, organizations, organizations irrespective of patterns of ownership according to their competence shall:
To organize 1) on subjects to protection studying and accomplishment of these rules by all engineering employees, employees and workers;
To organize 2) on subjects to protection voluntary fire teams and to approve procedure for their activities by the internal order (according to regulatory legal acts of the Kyrgyz Republic);
3) to organize carrying out on subjects to protection of fire-proof instructing and classes in fire technically minimum according to appendix 5 to these rules;
To establish 4) in production, administration, storage and auxiliary rooms high fire prevention regime (to determine and equip smoking areas, to determine places and the admissible number of one-time storage of raw materials and finished goods, to establish accurate procedure for carrying out hot work) and to constantly control its most strict observance by all employees of subject to protection;
5) to determine inspection routine and closings of rooms of different functional purpose after completion of work, with maintaining the magazine by form according to appendix 8 to these rules;
6) periodically to check condition of fire safety of subject to protection, availability and operability of technical means of fire-fighting, readiness of object fire protection and voluntary fire team and to take necessary measures to improvement of their work, with log entries in form according to appendix 7 to these rules;
7) to provide subject to protection with the signs given in appendix 6 to these rules.
4. The head of the organization provides content of fire trucks in fire stations or boxes which are specially intended for these purposes having heating, electric utility service, telephone communication, hard surface of floors, the warmed gate, other devices and the equipment necessary for providing normal and safe working conditions of staff of fire protection.
5. The head of the organization provides serviceable technical condition of fire trucks and motor-pumps, and also the equipment adapted (re-equiped) for suppression of the fires.
6. The head of the organization behind each fire motor-pump and the equipment adapted (re-equiped) for suppression of the fires will organize fixing of the mechanic (driver) who had special training for work on the specified equipment.
7. Only persons after training to measures of fire safety are allowed to work on subject to protection.
Training of persons in measures of fire safety is performed by carrying out fire-proof instructing and passing of fire and technical minimum.
The procedure and terms of carrying out fire-proof instructing and passing of fire and technical minimum are determined by the head of the organization.
8. Fire-proof training of engineering employees, employees and workers consists of fire-proof instructing (primary and secondary) and classes in fire technically minimum.
9. For passing of fire-proof instructing and classes in fire technically minimum on subjects to protection it is necessary to allocate the room equipped with necessary visual aids (posters, schemes, prototypes), and also samples of all types of the emergency firefighting equipment, fire stock and fire communications which are available on subject to protection.
10. Upon termination of passing of the program of fire and technical minimum at workers and employees offsettings are accepted. Results of carrying out offsettings on fire technically minimum are drawn up in magazines in the forms given in appendix 5 to these rules.
11. In storage, production, administration and public places, places of outdoor storage of substances and materials, and also placements of technological installations the head of the organization provides availability of plates with phone number for challenge of authorized state body in the field of fire safety.
12. On subject to protection with night stay of people (including at boarding schools, the organizations of social servicing, nursing homes, orphanages, the preschool educational organizations, hospitals and objects for summer children's holiday) the head of the organization will organize the round-the-clock watch of service personnel.
13. On subject to protection with night stay of people the head of the organization provides:
1) instruction availability about operations procedure of service personnel on case of emergence of the fire in day and night time, telephone communication, electric lamps (at least 2 lamps), individual protection equipment of respiratory organs and sight of the person from toxic products of burning;
2) daily transfer to division of authorized state body in the field of fire safety around which departure there is subject to protection with night stay of people, information on the number of the people who are on this object (including at night, in days off and holidays).
14. The head of the organization provides content of outside fire-escapes and barriers on roofs (coverings) of buildings and constructions in good repair, will organize at least 1 time in 5 years carrying out operating tests of fire-escapes and barriers on roofs, with creation of the corresponding test report, and also periodic survey of condition of survival equipment from height according to technical documentation or the passport of such product.
15. The territory of the companies, organizations, apartment houses and other objects, and also the territory adjoining to them shall be kept constantly clean and be cleared systematically of production wastes, combustible garbage, fallen leaves and dry grass. The production waste and packaging materials which are not subject to utilization shall be removed systematically on specially allotted sites and be exported timely.
16. To all buildings and constructions, fire water sources the open entry shall be provided. The condition of roadbed shall not interfere with journey of special fire-proof vehicles.
Drives and entrances to buildings, constructions and fire water sources, and also approaches to fire stock and the equipment, means of the notice on the fires, stationary fire-escapes shall be always free (at all seasons of the year) and be lit at night. It is forbidden on drives for the fire fighting equipment to arrange barriers, borders, to establish the metal barriers narrowing or interfering journey of special vehicles.
Requirements to drives for fire fighting automotive equipment it is determined by the regulatory legal acts and rules approved by authorized state body in the field of architectural and construction activities and housing and communal services.
17. It is forbidden to use fire-proof distances between buildings, constructions and structures, the turning and special platforms intended for installation of the rescue and fire fighting equipment, for warehousing of materials, the equipment and container, the parking of transport, construction of buildings and constructions (installations), cultivation of fires and burning of waste and container.
18. When carrying out repair work of the roads or drives connected with their closing, the head of the organization performing repair (construction) represents to division of authorized state body in the field of fire safety the relevant information on terms of carrying out these works and provides installation of the signs designating the direction of detour or arranges moving through the repaired sections of roads and drives.
19. Moving and transitions through inside railway tracks shall be free for journey of fire trucks and have continuous floorings at the level of top of heads of rails.
The number of moving shall be at least two. The parking of cars without locomotives on moving is forbidden.
20. On sites of the territory of subject to protection where accumulation of explosive mixes is possible, journey of vehicles is forbidden, about it the corresponding signs and texts shall be placed.
21. In the territory of explosive and fire-dangerous subjects to protection (if it is not connected with engineering procedure of production), and also in storage locations and conversions of combustible materials use of naked flame is forbidden.
22. Light priyamk at window openings of basement and first floors of buildings, constructions shall be cleared of garbage and foreign objects.
23. The container from under paints and varnishes shall be stored on the special platforms located at distance at least 20 meters from buildings and constructions and shall be densely closed.
24. Temporary storage of fuel in the yard, in the specially allotted place, not closer than 5 meters from buildings, fire hydrants and reservoirs is allowed.
25. Smoking in the territory of subject to protection is allowed only in the specially allotted places equipped with ballot boxes, reservoirs with water and designated by the corresponding texts and signs.
In the territory where smoking is forbidden, the prohibiting texts or signs are placed on foregrounds.
26. Around the settlements located in forests the actions excluding possibility of transfer of fire in case of the forest and peat fires on buildings and constructions shall be executed (the device of protective fire-proof strips, landing of deciduous plantings, removal during the summer period of dry vegetation).
27. It is forbidden to use the territories of fire-proof distances from objects and constructions of different function to forests (forest parks), places of development or open bedding of peat under construction of different constructions and subsidiary structures, and also for warehousing of combustible materials, garbage, waste of wood, construction and other combustible materials.
28. It is forbidden in the territory of settlements and city settlements, and also at distance less than 100 meters from forests to start uncontrollable products from combustible materials which principle of rise on height is based on heating of air in design by means of naked flame.
29. On subjects to protection it is forbidden:
1) to store and apply on attics, in cellars and first floors flammable and combustible liquids, gunpowder, explosives, pyrotechnic products, cylinders with combustible gases, goods in aerosol package, celluloid and other explosion-fire-hazardous substances and materials, to apply in garrets as heater peat, sawdust and other combustible materials;
2) to make change of space-planning decisions and placement of engineering communications and the equipment as a result of which access to fire extinguishers, fireplugs and other systems of ensuring fire safety is limited or the action area of automatic fire protection systems decreases (the automatic fire alarm, stationary automatic installation of fire extinguishing, system of smoke removal, the warning system and management of evacuation), to paint or stick with wall-paper automatic fire announcers;
3) to carry out cleaning of rooms and washing of clothes using gasoline, kerosene and other flammable and combustible liquids, and also to make warming of the frozen pipes blowtorches and by other methods using naked flame;
4) to operate electrical wires and cables with visible violations of isolation;
5) to use the damaged sockets, knife switches and other electroinstallations;
6) to wrap electrolamps and lamps paper, fabric and other combustible materials, and also to operate lamps with the taken-off caps (lenses) provided by lamp design;
7) to use the electroirons, rangettes, electric kettles and other electric heaters which do not have devices of thermal protection and also in case of absence or defect of the temperature regulators provided by design;
8) to use non-standard (self-made) electric heaters;
To leave 9) unguarded included in power network in electric heaters, and also other electrical household appliances including which are in waiting mode, except for electric devices which shall be in the round-the-clock operating mode according to the instruction of manufacturing plant;
10) to place in electropanel board combustible (including flammable) substances and materials;
11) to violate requirements to storage of the chemicals and materials given in appendix 2 to these rules;
12) when carrying out emergency and other construction and restoration works to use temporary electrical wiring, including extenders, surge protectors which are not intended according to the characteristics for power supply of the used electric devices.
Indicators of fire-and-explosion hazard and fire risk of substances and materials are determined by the regulatory legal acts and rules approved by authorized state body in the field of architectural and construction activities and housing and communal services.
30. On all subjects to protection floor-by-floor plans of evacuation of people and material values for case of emergence of the fires and emergency situations according to the interstate standard "Systems Evacuation Photoluminescent" shall be placed (GOST 34428-2018).
On plans of evacuation the main and emergency exits, and also the locations of emergency firefighting equipment and bonds are designated.
31. Locks on doors of emergency exits shall provide possibility of their free opening without key from within.
The head of the organization on which subject to protection there was fire provides access to fire divisions to the enclosed space for the purposes of fire extinguishing and carrying out wrecking.
32. In case of operation of evacuation ways, emergency and emergency exits it is forbidden:
1) to arrange on the ways of evacuation thresholds (except for thresholds in doorways), the false doors having similarity to these doors, to establish sliding and lifting and lowering doors and gate, revolving doors and tourniquets, and also other devices interfering free evacuation of people, to establish in staircases of mirror and external blocks of conditioners;
2) to encumber evacuation ways and exits (including passes, corridors, platforms, galleries, lift halls, landings, marches of ladders, doors, evacuation hatches) different materials, products, the equipment, production waste, garbage and other objects, to block doors of emergency exits, and also to close on the lock of door of emergency exits and to kill them tightly;
3) to arrange in platforms of exits (except for apartments and individual apartment houses) dryers and hangers for clothes, clothes, and also to store (including it is temporary) stock and materials;
4) to fix the self-closed doors of staircases, corridors, halls and platforms in open provision, and also to remove the doors interfering distribution of dangerous factors of the fire on the ways of evacuation;
5) to replace armored glass regular in glazing of doors and transoms;
To place 6) in lift halls storage rooms, booths, stalls and other similar rooms;
To encumber 7) with furniture, the equipment and other objects of door, hatches on balconies and loggias, transitions to adjacent sections and exits to outside evacuation ladders, to dismantle interbalcony ladders, to make hatches on balconies and loggias of apartments;
8) to glaze the balconies, loggias and galleries conducting to nezadymlyaemy staircases;
To arrange 9) on staircases and floor-by-floor corridors storage rooms and other utility rooms, and also to store under ladder marches and on landings of thing, furniture and other combustible materials, to lay industrial gas pipelines and steam lines, pipelines with flammable and combustible liquids, electric wires and cables (except for electrical wiring for illumination of corridors and staircases);
10) to encumber and close passes to places of fixture of rescue devices.
33. It is forbidden to leave upon termination of working hours not deenergized electroinstallations and electrical household appliances in rooms in which there are no personnel on duty, except for of emergency lighting, fire protection systems, and also other electroinstallations and electrotechnical devices if it is caused by their functional purpose or it is provided by requirements of the maintenance instruction.
34. In corridors, on landings and on the doors conducting to emergency exits or directly outside the ordering signs "EXIT" connected to emergency lighting system in case of the fire shall be established.
35. Wooden structures of garrets shall be processed by fireproof structure. Quality of fireproof processing shall be controlled annually and, if necessary, be exposed to repeated processing.
36. Doors (hatches) of attics, technical floors, basements, electropanel board and air-ventilation chambers shall contain in the closed condition on the lock. Keys from locks shall be stored in the certain place available to obtaining them at any time (the apartment on upper floor, the commandant, protection).
On doors garret and basements, technical floors there shall be texts about the storage location of keys.
It is necessary to place schemes of their layout with entrances to cellars and technical floors.
Intersection doors of garrets, and also doors in fire-proof walls (partitions) shall reside in the closed condition.
37. It is forbidden to make facing of combustible materials (pasting by combustible film materials), and also of the fire-resistant finishing materials emitting when burning toxic substances, walls and ceilings in general corridors, in staircases, lobbies, halls and the foyer and also to arrange from combustible materials floors in lobbies, staircases and lift halls.
Coverings of floors (carpets, carpet paths) on the ways of evacuation (corridors, the foyer, lobbies, halls, ladders) in visual, exhibition, exposition, reading rooms and other rooms with mass stay of people shall be strictly attached to floor.
Application of carpets and carpet paths from synthetic combustible materials is forbidden.
37. Use of elevators and elevators for evacuation of people in case of the fire is forbidden.
The procedure for use by the organizations of the elevators having operating mode "transportation of fire divisions" is regulated by the instruction approved by the head of the organization. The specified instructions shall be hung out directly at governing bodies of elevator cabin.
The head of the organization provides nezadymlyaemost of lift halls of the elevators used as safety areas for handicapped national groups and other citizens by maintenance in good repair of fire-proof barriers (partitions) and fillings of apertures in them, appropriate means of individual protection and communication with the room of fire post, and also signs of fire safety specifying the direction to such zone.
39. On subjects to protection with mass stay of people, school and preschool educational institutions, houses for elderly citizens and persons with limited opportunities of health, medical and improving institutions with hospital installation of metal lattices at windows is forbidden.
40. Apertures in fire-proof walls and overlappings shall be equipped with protection devices against spread of fire and products of burning (fire-proof doors, water veils, gates, shiber, antismoke devices) which shall contain in operating state constantly.
When crossing fire-proof barriers different communications gaps between them and designs of barriers (on all thickness) shall be tightly closed up by nonflammable material.
41. In workshops and laboratories where flammable and combustible liquids and gases are applied, it is necessary to provide centralized transportation and their distribution on workplaces. In all other cases it is necessary to apply safe container of special design to transferring of flammable and combustible liquids.
For shop storage rooms the most admissible number of one-time storage of flammable and combustible liquids shall be normative established. On workplaces it is possible to keep such amount of materials (in type, ready to application) which does not exceed replaceable requirement. At the same time reservoirs shall be densely closed.
42. Production rooms and their equipment shall be cleared periodically of dust and other combustible waste. In places of intensive allocation of waste in the form of dust indicators of their fire risk shall be determined.
43. The special clothes of working personnel shall be stored in certain rooms. By administration of subject to protection for each division (production operation) the replacement procedure of the oiled clothes on net shall be established. In pockets of special clothes it is forbidden to leave the oiled rags and cleaning rags.
44. It is forbidden to dry clothes, footwear in rooms, and also to have any combustible materials on the hot surfaces of pipelines, devices and devices of heating. For drying of clothes, footwear it is necessary to provide special places.
45. The hot surfaces of the pipelines passing in rooms in which are possible ignition of materials, explosion of explosive mixes need to be isolated nonflammable materials.
46. In explosive rooms and it is forbidden to work at explosive installations in the footwear padded with steel nails or horseshoes.
47. In case of work in rooms where formation of explosive mix with air is possible, it is necessary to use the tool manufactured of the metal which is not giving in case of blow of sparks, and the cutting steel tool needs to be covered with jellied lubricants plentifully.
48. On transactions of sink and degreasing of details it is necessary to apply fireproof technical detergents.
49. Smoking on objects of trade, production, conversion and storage of flammable and combustible liquids and combustible gases, on objects of production of all types of explosives, explosion-fire-hazardous and fire-dangerous sites is forbidden.
The head of the organization provides placement in the specified territories of signs of fire safety "Tobacco smoking and use of naked flame is forbidden".
The places specially allotted for smoking are designated by the signs "Smoking area".
50. Before heating season it is necessary to perform checks and repair of furnaces, boiler, heatgenerating, calorifer installations and fireplaces, and also other heating devices and systems.
It is forbidden to operate furnaces and other heating devices without fire-proof cutting (отступок) from combustible designs, the prefurnace sheets made of nonflammable material by the size are at least 0,5⨯0,7 meter (on wooden or other floor from combustible materials), and also in the presence of progar and damages to cutting (otstupka) and prefurnace sheets.
51. Before heating season, and also during the heating season it is necessary to provide carrying out cleaning of flues and furnaces (heating devices) from soot.
52. In case of operation of the boiler and other heatmaking installations it is forbidden:
To allow 1) to work of persons which are not instructed about measures of fire safety;
To apply 2) in fuel quality waste oil and other flammable and combustible liquids which are not provided by specifications on operation of the equipment;
3) to operate the heatmaking installations in case of dribble of liquid fuel (gas leakage) from systems of fuel feeding, and also gates at fire chamber and at reservoir with fuel;
4) to give fuel in case of extinct nozzles or gas torches;
5) to kindle installations without their preliminary purge;
6) to work in case of the defective or switched-off devices of control and regulation provided by manufacturer;
7) to dry any combustible materials on coppers and steam lines;
8) to operate the boiler installations using solid fuel which chimneys are not cleared of soot.
53. In case of operation of oven heating it is forbidden:
To leave 1) unguarded furnaces which burn, and also to charge supervision of them to children;
2) to have fuel, other combustible substances and materials on prefurnace leaf;
To heat 3) coal, coke and gas of the furnace, the fuels which are not intended for these types;
4) to use ventilating and gas channels as flues;
5) to perekalivat furnaces.
54. The fire chamber of furnaces in buildings and constructions (except for apartment houses) shall stop at least in 2 hours prior to completion of work, and in hospitals and other subjects to protection with the round-the-clock stay of people - in 2 hours prior to withdrawal of patients to dream.
The ashes and slag removed from fire chambers shall be filled in with water and are removed to the place, specially allotted for them.
55. Goods, racks, show-windows, counters, cases and other equipment are located at distance of at least 0,7 of meter from furnaces, and from furnace openings - meter 1,25 suffices.
In case of operation of metal furnaces the equipment shall be located at distance at least than 2 meters from the furnace.
56. The head of the organization provides whitewashing of chimneys and walls in which there pass smoke channels.
57. In case of operation of the heatgenerating devices it is forbidden:
1) to work at the device with the broken hermeticity of fuel-supply lines and in case of the defective locking valve on it, leaky connections of the case of nozzle with the heatgenerating device, defective flues, electric motors and devices of protection, and also in the absence of thermal protection of the electric motor and other defects;
2) to work at the device with open fuel tanks;
3) to work in case of not adjusted nozzle (with fuel delivery violation);
4) about the device and account tanks to arrange barriers from materials of groups of combustibility G3-G4, classification of which is determined by the regulatory legal acts and rules approved by authorized state body in the field of architectural and construction activities and housing and communal services;
5) to warm fuel-supply lines open flame;
6) to light working mix through viewing peephole;
7) to regulate gap between electrodes of candles in case of the working heatgenerating device;
8) operation of the heatgenerating device in case of absence and defect of protective lattice on airintaking collectors;
9) to leave the working heatgenerating devices unguarded;
10) to violate service conditions of the heatgenerating devices, to place them in rooms (places), unadapted for these purposes.
58. Electric heaters need to be allowed to application with the operational alarm system and blocking excluding supply of electricity on heating elements in case of the idle fan and automatic equipment of control of temperature of the coming-out air and its regulation provided by electric and thermal protection.
59. In case of operation of heaters it is forbidden:
1) to switch-off the alarm system or blocking;
2) to apply combustible materials to flexible insert between the case of electric heater and the fan;
3) to exceed the maximum permissible air temperature at the exit from electric heater established by manufacturing plant;
4) to include electric heater in case of the idle fan (blocking is checked before each start-up of installation);
5) to dry clothes or other combustible materials on electric heater or near it.
60. Fire-retardant devices (gates, shiber, valves) in air ducts, devices of blocking of ventilating systems with automatic installations of the fire alarm or fire extinguishing, automatic devices of shutdown of ventilation in case of the fire shall be checked in the terms established by technical documentation and contain in good repair.
Sensitive elements of the drive of latches (fusible locks, easily combustible inserts, thermosensitive elements) shall be cleared of pollution by combustible dust timely.
61. Storage in air-ventilation chambers any the equipment and materials is forbidden. Air-ventilation chambers shall be closed constantly on the lock. The entrance is forbidden to strangers in air-ventilation chambers.
62. Operation of processing equipment in rooms with explosion-fire-hazardous productions in case of defective hydrofilters, pyleotsasyvayushchy, dust removal and other devices of systems of ventilation is forbidden.
63. In production rooms in which ventilating devices transport combustible and explosive substances all metal air ducts, pipelines, filters and other equipment of exhaust installations shall be grounded.
64. Air-ventilation chambers, cyclones, filters, air ducts shall be cleared of combustible dust and production wastes. Check, routine inspection and cleaning of the ventilating equipment shall be made according to the schedule approved by the director or workshops. Results of surveys are surely entered in the special magazine.
65. Exhaust air ducts on which explosive or combustible dust is transported shall have devices for periodic cleaning (hatches, folding connections).
66. The ventilating installations servicing explosion-fire-hazardous rooms shall have remote devices of their inclusion or shutdown in case of the fires or accidents according to the requirements which are specially caused for each room and to contain in good repair.
67. At least once a quarter it is necessary to check quality of fire protection of air ducts and, in case of violation of integrity of fireproof covering, to take measures for its recovery.
68. In case of operation of ventilating systems it is forbidden:
1) to disconnect or dismantle fire-retardant devices;
2) to use ventilating channels as flues;
Disclaimer! This text was translated by AI translator and is not a valid juridical document. No warranty. No claim. More info
Database include more 50000 documents. You can find needed documents using search system. For effective work you can mix any on documents parameters: country, documents type, date range, teams or tags.
More about search system
If you cannot find the required document, or you do not know where to begin, go to Help section.
In this section, we’ve tried to describe in detail the features and capabilities of the system, as well as the most effective techniques for working with the database.
You also may open the section Frequently asked questions. This section provides answers to questions set by users.